The VPU AC II TERMINAL PLUG is the first pluggable Type II surge protection device for SNAP IN terminal blocks. Mounted directly on the feed-in power terminals, it saves space and wiring effort, shortens installation time and reduces potential sources of error.

The practical 0 m connection cable supports standards-compliant installation in accordance with EN 60364-4-443 and improves protection performance. For testing or replacement, the module can be easily levered out with a screwdriver and plugged back in – ideal for sub-distributions in building, industrial and retrofit applications.

The benefits at a glance

Minimal wiring effort

Minimal wiring effort

The SNAP IN connection technology used in the terminal blocks enables quick, secure and tool-free installation.

Standard-compliant

Standard-compliant

By plugging the surge protection device directly into the terminal blocks, the ‘0.5 m connection rule’ required by EN 60364-4-443 is complied with.

Compact design

Compact design

The pluggable surge protection can be retrofitted for space-saving installation. If the connection terminals are of a different type, a suitable terminal block set is available.

Technical data

  • Imax: 40 kA / 65 kA (L-N / N-PE) (8/20 µs)
  • Pluggable modules for the SL series
  • Full-featured Type II+III surge protection
  • Universal 3+1 circuit

Pluggable surge protection

Pluggable surge protection modules reduce installation errors and, in the event of maintenance, allow for quick replacement without the need for complex rewiring or downtime.

Practical status monitoring

The TERMINAL PLUG has a status window as a function indicator. In the event of an overload, the mechanical status monitoring system is enabled and displays a red status window.

Fast wiring with SNAP IN

The VPU AC II TERMINAL PLUG brings pluggable Type II surge protection directly to SNAP IN terminal blocks. This saves space and wiring effort, speeds up installation, and simplifies testing, maintenance, and replacement.

Status monitoring with a remote signalling contact

Modules with a remote contact enable remote monitoring of the module status. ‌This allows service calls to be planned in a targeted manner.

Space-saving thanks to direct wiring

IEC 60364-5-53 and DIN VDE 100-543 define how a surge protection device must be installed:​ The line length from the connection point of the surge protection device on the active conductor to the connection point of the surge protection device to earth must not exceed 0.5 m.​

Thanks to the direct plug connection onto the terminal block, there is no need for an additional protection module or wiring. The relevant line length is 0 m and therefore complies with the standard installation requirements.

Definition of connection point:​
The connection point refers to the nearest screw, terminal or plug-in connection between the cable connected to the surge protection device and the relevant live conductor or the earthing system. This may be a terminal block, an earthing screw or a copper busbar connection, or a connection point on another device such as a main switch.​